NETLOG is a programmable
controller (PLC) engineered in a DIN43880 enclosure, member of Netsyst family
controllers.
The base module provide 12 optoisolated digital input, 8
isolated digital output, 4 analog inputs 0-10V (or RTD) 16bit resolution,
2 analog outputs 0-10V. Each digital input/output is equipped with LED status
indicator.
The Base version is equipped with 2 serial ports and, RS485
versions, are provided of interface galvanically insulated with Fail safe
high input impedance driver that allows up to 128 devices on the same
network.
The device can be expanded with the 10I/O and/or 20I/O extension
modules through its I2C™ bus, up to 7 extension modules can
be connected.
For the connection of the extension modules it is necessary
to use the proper bus extension cables (Code CBL045**00) to be ordered separately, and available in two different lengths according to cabling requirements.
| Features |
| |
Lite version |
Base version |
| CPU |
Processor |
80C32 Code compatible 12MIPS |
80C32 Code compatible 10MIPS peak |
| Program memory: |
62Kbytes FlashEprom |
128Kbytes FlashEPROM |
| Data memory: |
2Kbytes |
24Kbytes RAM battery backup |
| On board mass memory |
None |
60Kbytes EEPROM
(From Kernel SFW146G400) |
| Real Time clock/cal.: |
None |
Yes |
| Battery |
None |
Lithium endurance 10years Typ. |
| Digital
inputs |
12 Optoisolated PNP/NPN 10-30Vdc,
5mA@24V |
| Digital
output |
Relay version |
8 Relay 5A@250Vac 1 common |
| Static version |
8 Static 350mA 0-60Vdc
PNP/NPN |
| Analog
inputs |
Resolution |
16bit (0-10Vdc, 0-1.25Vdc)
+/-0.01°C (PT100/PT1000) |
| Nr/Type |
4 * 0-10Vdc or 0-1.25Vdc or 0-20mA (common
mode)
2 RTD with excitation 200uA (differential mode) |
| Linearization |
RTD Method Kallendar-Van Dusen |
| Acq. freq.: |
105Hz (voltage/current), 5.35Hz (temperature) |
| Analog outputs |
1 * 0-10Vdc 10mA max (PWM 16bit)
1 * 0-10Vdc 10mA max (DAC 12bit) |
| Expandability |
up to 7 modules through the I2C
bus |
| Field Bus |
none |
None (basic ver.) |
| RS485 isolated (RS485 ver.) (1) |
| CAN isolated (CAN ver.) |
| RS232 I/F |
1 * DTE on RJ45 connector |
2 * DTE on RJ45 connector |
User I/F
(optional) |
Display: |
none |
STN 2*16 characters LED Backlight |
| Keyboard: |
none |
6 membrane keys |
| Status indicators |
System Ready
RUN (Field CPU)
RUN (Main CPU) (From Rel. B)
DTR Status
I/O Status |
| Power supply |
10-30Vdc 2W |
10-30Vdc 3W |
| Environment |
Operating temp. |
from -20 to +70 °C |
| Storage temp. |
from -40°
to +80 °C |
| Humidity |
Max. 90% |
| Dimensions
and weight |
Dimensions: |
160 mm L x 90 mm W x 58 mm H |
| Weight: |
300g |
400g |
| Approvals |
CEI EN50081-1
CEI EN50082-2 |
| Warranty |
2 Years |
| Remote programming |
No |
Yes, fom release B |
Notes
(1) Available protocols: Modbus RTU, Modbus ASCII, DMX |
I2C™è un marchio registrato di
Philips Semiconductors |
 |
The I/O's connections are made through extractable TB for
an easier maintenance.
The apparatus accept an extended power from 10 to 30Vdc.
The ability to operate with 12Vdc power facilitates the solution of a variety
of applications in domotics, automotive and, generally, whereas a battery
power is required.
Netlog may be supplied with RS485 field bus (Modbus RTU or
ASCII protocol), to connect it with other devices provided of this interface.
The programming is made through the development tool Remoter.
It allows the Ladder Diagram (LD), Instruction List (IL) and/or C Language programming,
allowing the developing of applications difficultly approachable with concurrent
products with similar price.
Netlog is available in "Base" or "Lite"
version. The Lite version is recommended in applications were the cost is
a critical factor, and it doesn't provide integrated user interface and
Real time clock/calendar.
The "Display" version is equipped with a 6Keys
Keypad and alphanumeric LCD display 2 lines * 16 characters.
The device is dimensionally and for most connections compatible
with the previous series of Netlog.
The CPU
module installed in the products has a kernel program preinstalled,
to upgrade it please follow the information reported in the related FAQ.
NetlogII is available in OEM version also, oriented to the
users that need to realize semi custom devices extremely cost sensitive.
Due the support of Modbus Rtu protocol, can be connected operator terminals, SCADA software, ProfiLab-Expert applications.
To know what you need to begin with this product click
here |